Mike Krzyzewski is really a famous coach of Dream Team. She has coached north america men's basketball team for some time, that's clinched numerous medals for his country. Following Londonfl jerseys supplyn Olympic was over, Krzyzewski told The Associated Press that this game will be his final one as national coach, a job he's held for seven years. He had left open the possibility of swomen nfl jerseystaying with the team beyond the London Games, when practice on Saturday said these will be his last Olympics.When asked if he was sure, Krzyzewski didn't hesitate before again saying, "yecheap nfl jerseys wholesales," this will be his last game "If we could win it, then it might be three major championships in a row, i always do not know when that has been done because we haven't usually won http://govoriotkrito.bg/libs/nflcn08.htmthe globe championships," Krzyzewski said. "It becomes an enormous thing for the program." Whatever, he's an awesome coach. His achievement are going to be remembered by the country.cheap nfl jerseys
  • <sup id="cpttk"><center id="cpttk"><input id="cpttk"></input></center></sup>

  • <mark id="cpttk"><center id="cpttk"><dl id="cpttk"></dl></center></mark><s id="cpttk"></s>
  • <s id="cpttk"><i id="cpttk"><form id="cpttk"></form></i></s>

      1. 高壓真空斷路器技術(shù)參數(shù)

        2014/1/3 8:19:18      點(diǎn)擊:
        高壓真空斷路器 技術(shù)參數(shù)參數(shù)名稱 單位 型號(hào)
        ZN28-12/1250-20 ZN27-12/1250-31.5 ZN27A-12/3150-40
        電壓參數(shù)
        額定電壓 kV 10
        最高電壓 11.5
        絕緣水平
        工頻耐壓 極間、極對(duì)地 42
        斷口間 48
        沖擊耐壓 極間、極對(duì)地 75
        斷口間 84
        電流參數(shù) 額定電流 A 1250 1250 3150
        額定短路開斷 kA 20 31.5 40
        額定峰值耐受電流 kA 50 80 100
        4S短時(shí)耐受電流 kA 20 31.5 40
        額定短時(shí)關(guān)合電流(峰值) kA 50 80 100
        額定單個(gè)電容器組開斷電流 A 630 800
        額定背對(duì)背電容器組開斷電流 A 400 400
        壽命 額定短路開斷電流次數(shù) 次 50 50 30
        機(jī)械壽命 次 10000
        其它 額定操作順序 分-0.5s-合分-180s-合分 分-180s-合分-180-合分
        全開斷次數(shù) 不大于60
        配用操動(dòng)機(jī)構(gòu) CD或CT機(jī)構(gòu)
        機(jī)械特性

        (運(yùn)行參數(shù)) 序號(hào) 機(jī)械特性參數(shù) 單位 ZN28-12/1250-20 ZN27-12/1250-31.5 ZN27A-12/3150-40
        1 觸頭開距 mm 11±1.0 10±1.0 11±1.0
        2 接觸行程 mm 4±1.0 3±0.5
        3 觸頭接觸壓力 N 1500±200 3000±200 5000±300
        4 平均合閘速度 m/s 0.6±0.2
        5 平均分閘速度 m/s 1.1±0.2 1.1±0.3 1.1±0.3
        6 合閘彈跳時(shí)間 ms <2
        7 分、合不同期性 ms <3
        8 合閘時(shí)間 ms <100
        9 分閘時(shí)間 ms <60
        10 主回路直流電阻 μΩ ≤60 ≤60 ≤20
        11 動(dòng)靜觸頭累積允許磨損厚度 mm 3.0
        為滿足真空滅弧室對(duì)機(jī)械參量的要求,保證真空斷路器電氣機(jī)械性能,確保運(yùn)行可靠性,真空斷路器須具有穩(wěn)定、良好的機(jī)械特性。主要機(jī)械特性列于上表,亦以三種斷路器技術(shù)指標(biāo)為例。 4.各機(jī)械特性對(duì)產(chǎn)品性能的影響 產(chǎn)品機(jī)械特性的優(yōu)劣,對(duì)產(chǎn)品各項(xiàng)電氣性能有重要的關(guān)系,而且影響產(chǎn)品運(yùn)行可靠性。衡量真空斷路器的性能,真空滅孤室本身的性能固然重要,然而機(jī)械特性同樣具有舉足輕重的作用。下面對(duì)各機(jī)械特性參數(shù)與產(chǎn)品性能的關(guān)系分述如下:
        開距

        觸頭的開距主要取決于真空斷路器的額定電壓和耐壓要求,一般額定電壓低時(shí)觸頭開距選得小些。但開距太小會(huì)影響分?jǐn)嗄芰湍蛪核。開距太大,雖然可以提高耐壓水平,但會(huì)使真空滅弧室的波紋管壽命下降。設(shè)計(jì)時(shí)一般在滿足運(yùn)行的耐壓要求下盡量把開距選得小一些。10kV真空斷路器的開距通常在8~12mm之間,35kV的則在30~40mm之間。
        接觸壓力

        在無(wú)外力作用時(shí),動(dòng)觸頭在大氣壓作用下,對(duì)內(nèi)腔產(chǎn)生一個(gè)閉合力使其與靜觸頭閉合,稱之為自閉力,其大小取決于波紋管的端口直徑。滅弧室在工作狀態(tài)時(shí),這個(gè)力太小不能保證動(dòng)靜觸頭間良好的電接觸,必須施加一個(gè)外加壓力。這個(gè)外加壓力和自閉力之和稱為觸頭的接觸壓力。這個(gè)接觸壓力有如下幾個(gè)作用:
        (1)保證動(dòng)、靜觸頭的良好接觸,并使其接觸電阻少于規(guī)定值。
        (2)滿足額定短路狀態(tài)時(shí)的動(dòng)穩(wěn)定要求。應(yīng)使觸頭壓力大于額定短路狀態(tài)時(shí)的觸頭間的斥力,以保證在該狀態(tài)下的完全閉合和不受損壞。
        (3)抑制合閘彈跳。使觸頭在閉會(huì)碰撞時(shí)得以緩沖,把碰撞的動(dòng)能轉(zhuǎn)為彈興的勢(shì)能,抑制觸頭的彈跳。
        (4)為分閘提供一個(gè)加速力。當(dāng)接觸壓力大時(shí),動(dòng)觸頭得到較大的分閘力,容易拉斷會(huì)鬧熔焊點(diǎn),提高分閘初始的加速度,減少燃弧時(shí)間,提高分?jǐn)嗄芰。觸頭接觸壓力是一個(gè)很重要的參數(shù),在產(chǎn)品的初始設(shè)計(jì)中要經(jīng)過(guò)多次驗(yàn)證、試驗(yàn)才選取得比較合適。如觸頭壓力選得太小,滿足不了上述各方面的要求;但觸頭壓力太大,一方面需要增大合閘操作功,另外滅弧室和整機(jī)的機(jī)械強(qiáng)度要求也需要提高,技術(shù)上不經(jīng)濟(jì)。
        接觸行程

        真空斷路器毫無(wú)例外地采用對(duì)接式接觸方式。動(dòng)觸頭碰上靜觸頭之后就不能再前進(jìn)了,觸頭接觸壓力是由每極觸頭壓縮彈簧(有時(shí)稱作合閘緩沖彈簧)提供的。所謂接觸行程,就是開關(guān)觸頭碰觸開始,觸頭壓簧施力端繼續(xù)運(yùn)動(dòng)至終結(jié)的距離,亦即觸頭彈簧的壓縮距離,故又稱壓縮行程。
        接觸行程有兩方面作用,一是令觸頭彈簧受壓而向?qū)佑|頭提供接觸壓力;二是保證在運(yùn)行磨損后仍然保持一定的接觸壓力,使之可靠接觸。一般接觸行程可取開距的20%~30%左右,10kV的真空斷路器約為3~4mm。
        真空斷路器的實(shí)際結(jié)構(gòu)中,觸頭合閘彈簧設(shè)計(jì)成即使處于分閘位置,也有相當(dāng)?shù)念A(yù)壓縮量,有預(yù)壓力。這是為使合閘過(guò)程中,當(dāng)動(dòng)觸頭尚未碰到靜觸頭而發(fā)生預(yù)擊穿時(shí),動(dòng)觸頭有相當(dāng)力量抵抗電動(dòng)力,而不致于向后退縮;當(dāng)觸頭碰接瞬間,接觸壓力陡然躍增至預(yù)壓力數(shù)值,防止合閘彈跳,足以抵抗電動(dòng)斥力,并使接觸初始就有良好狀態(tài);隨著接觸行程的前進(jìn),觸頭間的接觸壓力逐步增大,接觸行程終結(jié)時(shí),接觸壓力達(dá)到設(shè)計(jì)值。接觸行程不包括合閘彈簧的預(yù)壓縮量程,它實(shí)際上是合閘彈簧的第二次受壓行程。
        合閘速度

        平均合閘速度主要影響觸頭的電磨蝕。如合閘速度太低,則預(yù)擊穿時(shí)間長(zhǎng),電弧存在的時(shí)間長(zhǎng),觸頭表面電磨損大,甚至使觸頭熔焊而粘住,降低滅弧室的電壽命。但速度太高,容易產(chǎn)生合閘彈跳,操動(dòng)機(jī)構(gòu)輸出功也要增大,對(duì)滅弧室和整機(jī)機(jī)械沖擊大,影響產(chǎn)品的使用可靠性與機(jī)械壽命。平均合閘速度通常取0.6m/s左右為宜。
        分閘速度

        斷路器的分閘速度一般而言速度越快越好,這樣可以使首開相在電流趨近于0前2~3ms時(shí)能開斷故障電流;否則首開相不能開斷而延續(xù)至下一相,原來(lái)首開相變?yōu)楹箝_相,燃弧時(shí)間加長(zhǎng)了,增加了開斷的難度,甚至使開斷失敗。但分閘速度太快,分閘的反彈也大,反彈太大震動(dòng)過(guò)劇亦容易產(chǎn)生重燃,所以分間速度亦應(yīng)考慮這方面同素。分閘速度的快慢,主要取決于合閘時(shí)動(dòng)觸頭彈簧和分閘彈簧的貯能大小。為了提高分閘速度,可以增加分閘彈簧的貯能量,也可以增加合閘彈簧的壓縮量,這都必然需要提高操動(dòng)機(jī)構(gòu)的輸出功和整機(jī)的機(jī)械強(qiáng)度,降低了技術(shù)經(jīng)濟(jì)指標(biāo)。經(jīng)過(guò)多年試驗(yàn)認(rèn)為,10kV的真空斷路器,平均分閘速度能保證在0.95~1.2m/s比較合適。
        彈跳時(shí)間

        合閘彈跳時(shí)間是斷路器在合閘時(shí),觸頭剛接觸開始計(jì)起,隨后產(chǎn)生分離,可能又接觸又分離,到其穩(wěn)定接觸之間的時(shí)間。
        這一參數(shù)國(guó)外的標(biāo)準(zhǔn)中都沒(méi)有明確規(guī)定,1989年底能源部電力司提出真空斷路器合閘彈跳時(shí)間必須小于2ms。為什么合閘彈跳時(shí)間要小于2ms呢?主要是合閘彈跳的瞬間會(huì)引起電力系統(tǒng)或設(shè)備產(chǎn)生L.C高頻振蕩,振蕩產(chǎn)生的過(guò)電壓對(duì)電氣設(shè)備的絕緣可能造成傷害甚至損壞。當(dāng)合閘彈跳時(shí);同小于2ms時(shí),不會(huì)產(chǎn)生較大的過(guò)電壓,設(shè)備絕緣不會(huì)受損,在關(guān)合時(shí)動(dòng)靜觸頭之間也不會(huì)產(chǎn)生熔焊。
        合閘的不同期性太大容易引起合閘的彈跳,因?yàn)闄C(jī)構(gòu)輸出的運(yùn)動(dòng)沖量?jī)H由首合閘相觸頭承受。分閘的不同期性太大可能使后開相管子燃弧時(shí)間加長(zhǎng),降低開斷能力。
        合閘與分閘的不同期性一般是同時(shí)存在的,所以調(diào)好了合閘的不同期性,分閘的不同期性也就有了保證。產(chǎn)品中要求合分閘不同期性小于2ms。
        分、合閘時(shí)間是指從操動(dòng)線圈的端子得電時(shí)刻計(jì)起,至三極觸頭全部合上或分離止的一段時(shí)間間隔。
        合、分閘線圈是按短時(shí)工作制作設(shè)計(jì)的,合閘線圈的通電時(shí)間不到100ms,分閘線圈的不到60ms。分、合閘時(shí)間一般在斷路器出廠時(shí)已調(diào)好,無(wú)須再動(dòng)。
        當(dāng)斷路器用在發(fā)電系統(tǒng)并在電源近端短路時(shí),故障電流衰減較慢,若分閘時(shí)間很短,這時(shí)斷路器分?jǐn)嗟墓收想娏骶涂赡芎休^大的直流分量,開斷條件更為惡劣,這對(duì)斷路器的開斷是很不利的。所以用于發(fā)電系統(tǒng)的真空斷路器,其分閘時(shí)間盡可能設(shè)計(jì)長(zhǎng)些為宜。
        回路電阻

        回路電阻值是表征導(dǎo)電回路的聯(lián)接是否良好的一個(gè)參數(shù),各類型產(chǎn)品都規(guī)定了一定范圍內(nèi)的值。若回路電阻超過(guò)規(guī)定值時(shí),很可能是導(dǎo)電回路某一連接處接觸不良。在大電流運(yùn)行時(shí)接觸不良處的局部溫升增高,嚴(yán)重時(shí)甚至引起惡性循環(huán)造成氧化燒損,對(duì)用于大電流運(yùn)行的斷路器尤需加倍注意。回路電阻測(cè)量,不允許采用電橋法測(cè)量,須采用GB763規(guī)定的直流壓降法。
        觸頭系統(tǒng)

        “真空斷路器”的觸頭常采取對(duì)接式觸頭。因?yàn)橐话愕恼婵諗嗦菲髟诜珠l狀態(tài)下動(dòng)靜觸頭的距離只有16mm這么小的距離很難制作出其他形狀的接觸面,而且平直的接觸面瞬間動(dòng)作電弧的損傷也較小。真空斷路器的優(yōu)點(diǎn)之一是體積小,動(dòng)靜觸頭要在一個(gè)絕對(duì)真空的空間內(nèi)動(dòng)作,如果制作成其他的對(duì)接方式也會(huì)增加斷路器自身的體積!